变风量空调自动控制及节能技术相关外文翻译.doc
《变风量空调自动控制及节能技术相关外文翻译.doc》由会员分享,可在线阅读,更多相关《变风量空调自动控制及节能技术相关外文翻译.doc(29页珍藏版)》请在沃文网上搜索。
1、1、 外文原文(复印件)VAV SYSTEM ANALYSISXue Zhifeng,Chen Feng and Jiang YiTsinghua UniversityBeijing+100084 ChinaxuezhfABSTRACTThere are two kind of supply fan rotation speed control methods , one is the static pressure control method, the other is the float pressure control method. Simulation shows that the
2、y have different working point along the whole year. The supply air fan controlled with float pressure control method need low rotation speed and works on high efficiency, so the float pressure control method need only 30% fan operation energy of the static pressure control method .The layout of the
3、 air duct may influence the fan control method.INTRODUCTIONAs the VAV system is getting popular in China, many problems are rising from the design, the operation as well as controls (Jiang 1997).According to investigation on several VAV systems in Beijing, the energy consumption changes in the range
4、 as large as between factors 1 to 1.5 due to different in design and control.The supply fan rotation speed control method is one of the important factor that influence the VAV systems energy consumption. There two kind of control methods, One is the static pressure control method, which is set a sta
5、tic pressure at the fan export or at one point on the supply air duct. The other is the float pressure control method, using this mehthod , the supply air fan pressure head is just eaquel to the resistance of the supply air duct. The float pressure control method need the communication of the VAV bo
6、x, so it is difficult to realize. Most of the VAV systems in the comercial buildings in Beijing are using static pressure control method. But some research work consider the float pressure control method should be used(Sun,1997).There are two kinds of supply air duct layout, one is the tree type, an
7、d the other is the looping type (Goswami 1986 and I. Khoo 1997).Different duct layout influences the operating effect of static and float pressure control method.These former researches on the VAV systems control method and air duct layout are combined with the controller(for example PID),and they o
8、nly give some qualitative result. To guide the operation of VAV systems, this pape compare the different fan speed control stratergy with fan pressure head, rotation speed, efficiency and opration energy according to simulations. And also comparing the simulation result of looping and tree duct layo
9、ut.Table 1 Information of standard floorFigure 1 is the drawing of a commercial building in Tianjin of China. The middle is the machinery room, the around are office rooms. Each standard floor includes outer space and inner space. The depth of office room is about 15 meter. There are 30 floors in th
10、is building altogether. Table 1 shows the information of the building(standard floor).The external wall of the whole building is glass curtain wall.THE SUPPLY AIR AMOUNT AND THESUPPLY AIR TEMPERATUREUsing simulation software DeST (Chen,1999 and Jiang 1991),based on the whole year weather data, we ca
11、n calculate the whole year cooling and heating load of the building. The VAV systems have a variable supply air amount, so the supply air temperature varied also. The optimal temperature is the most energy saving. Knowing the cooling load and the supply air temperature, then we can get the supply ai
12、r amount of the whole year.The whole year supply air volume of outer space shows in Figure 2,the max min and ave represent the maximum minimum and average supply air volume of the same day from 8:00 in the morning to 17:00 in the afternoon.Figure 2:Supply air volume of the whole yearIn winter and su
13、mmer, some rooms in the building (for example north rooms in summer and south rooms in winter)have the large cooling or heating load of the all rooms, but the load of other rooms are little. In order to satisfy the room in each orientation, the supply air temperature can not be too high in winter an
14、d too low in summer. Figure 3 shows the whole year supply air temperature, the highest temperature is 32 C, and the lowest is 16 C.In winter and in summer, the difference with the supply air and the room temperature can not be very large. Then the coldest room of the building will need very large am
15、ount supply air volume .In the spring and the autumn, the situation is different, the cooling load difference of all the rooms are very little, so the supply air volume is between the maximum and minimum. In spring and autumn, the outdoor temperatures are between winter and summer, so the supply air
16、 volume is smaller than winter and summer. So in winter and summer the whole buildings supply air volume gets the maximum values. In spring and autumn the supply air volume is betweenthe winter and summer.Picture 3:Supply air temperature of the whole yearFigure 4 shows the supply air volume of the s
17、outh and the east orientation rooms. The largest supply air volume appears at different date.Figure 4:Supply air volume of the south and eastrooms of the buildingIn the following paper, we will compares the differen fan speed control strategy and supply air duct layout of this building combined with
18、 the supply air volume simulation results.FAN CONTROL STRATEGY OF TREEDUCTPicture 5 shows the one type supply air duct layout of the building refers in above paragraphs.Where AHU is the air-handling unit,1,2,39,10 are supply air duct number.With the known supply air volume, using simulation method,
19、we can get the fan pressure head of the whole year.Figure 6 shows the fan working point with three different control strategies.Figure 6:Fan working point with different control strategy of tree duct layoutWhere float present the float pressure control method. Static presents the static pressure con
20、trol method with static pressure point setting at the fan export .The part-sta present the static pressure control method with static pressure point at two part of the whole supply air duct(in Figure 5,it is at the export of duct 6).Where G present the supply air volume, P present the fan pressure h
21、ead.According to simulation results, we can see running in the same air volume, three different kinds of fan speed control strategy need different pressure head. The float pressure control methods pressure head is the lowest, while the static pressure control method with the static pressure setting
22、at the fan export needs the highest pressure head. The method with static pressure point setting at the two-part of the whole supply air duct needs fan pressure head between the other two kind methods.Different fan working points have different running efficiency. Choosing one kind of centrifugal su
23、pply air fan, using simulation method can get the fan efficiency for each working point according to the relation between the air volume, pressure head and fan running efficiency.The fan performance curve and fan efficiency curve also show in Figure 6.They come from the next formulas.Where:P is the
24、fan pressure head.G is the fan supply air volume.is the fan efficiency.n0 is the design fan rotation speed.n is the variable fan rotation speedIn Figure 6,some fan working point locate in the high efficiency area, others not. The area include most of the point working with static pressure point sett
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10 积分
下载 | 加入VIP,下载更划算! |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 风量 空调 自动控制 节能 技术 相关 外文 翻译