外文翻译 外文文献 英文文献 变压器励磁涌流的抑制.doc
《外文翻译 外文文献 英文文献 变压器励磁涌流的抑制.doc》由会员分享,可在线阅读,更多相关《外文翻译 外文文献 英文文献 变压器励磁涌流的抑制.doc(18页珍藏版)》请在沃文网上搜索。
1、Transformer inrush current suppression Transformer inrush current leads not only to the protective relaying misoperation, derived from the power grid voltage sags, harmonic pollution, and the inrush current, ferromagnetic resonance overvoltage in power system operation, to bring the negative effect
2、that cannot underestimate. For decades the people through the identification of inrush current feature method to reduce the relay misoperation rate, but did not gain a good return, malfunction rate is still high. As for the voltage sag, harmonic pollution, and the inrush current, elimination of the
3、more be nonplussed over sth. The reason is that people think the inrush current appears irresistible, can only use recognition countermeasure, namely hide countermeasure. In fact, change a train of thought - inhibition, can be fully realized, and have achieved. Introduction Transformer inrush and su
4、rge suppression capacitor chargingprinciple is completely similar to the inductance and capacitance are energy storage devices, the former does not allow current mutation, which does not allow voltage surge,power drop will induce a transient process. Access in the power transformer no-load transform
5、er outlet power failure andprotection devices to be removed, because of a side of the transformer windings to feel the surge applied voltage values are sometimes generated a great inrush current. Inrush currentpeak is not only large, and contains very many harmonics andDC component. Electrical equip
6、ment on the grid and thusresult in an extremely negative impact. 1. the danger of inrush current 1.1 caused by the transformer protection devices malfunction,the frequent failure of the transformer and put into operation;1.2 removal of the transformer short-circuit fault outlet voltage generated whe
7、n the sudden increase in the protection induced by transformermalfunction, so that each side of the transformer load all thepower;1.3 A power station access to a power transformer no-load inrush current generated, inducing other B power station nearby, C power station transformers are running a and
8、should surge (sympathetic inrush) and false tripping, resulting in a large area power failure; large inrush currentvalue of 1.4 would result in electric power transformers andcircuit breakers due to excessive damage; 1.5-induced over-voltage, damaged electrical equipment; 1.6 inrush current of the D
9、C component lead to over-current transformermagnetization and magnetic significantly reduce themeasurement accuracy and the correct action rate ofprotection devices; 1.7 magnetizing inrush current in a large number of harmonics on power quality caused by pollution.1.8 caused by voltage sags or swell
10、s, affecting the normal operation of other electrical equipment. For decades, people have taken to the inrush current approach is to hide, but because of inrush current form and characteristics ofdiversity, through mathematical or physical methods toidentify its characteristics difficult to improve
11、the accuracy ofthat inrush current in this field has been a historical problem. 2. the magnetizing inrush currentcauses Suppressor is an important feature of the strategy adopted bymagnetizing inrush current is not escape, but suppression. Inrush current theory and practice that can suppress or even
12、 eliminate, because the source of inrush current is generated in the transformer windings on either side felt the applied voltage increases, based on fluxconservation theorem, the windings in the magnetic circuit will produce a single polarity of the magnetic bias, such as partial pole and transform
13、er of exactly the same as the original remanence polarity, it may bias magnetic remanence andsteady-state flux superimposed with the result of magnetic saturation, thus greatly reducing the magnetizing reactance ofthe transformer windings , and then induced a significantinrush current value. As the
14、partial magnetic polarity and the value is applied voltage switch by selecting the phase angle control, and therefore, if we can grasp the power transformer when the last of remanent magnetic polarity, they can drop by when the control transformer the supply voltage phase angle, which allows magneti
15、c bias with opposite polarity remanence, which eliminate the inrush current of the soil -magnetic saturation, to achieve the inrush current . For a long time, people found it impossible to measure thetransformer polarity and remanence values, and thus had to abandon the use of the idea of partial re
16、manence magneticoffset. Inrush current in response to the strategy does notappear on the two smooth road, a road through the control power transformer voltage drop closing phase angle, so that it does not produce magnetic bias, in order to avoid magnetic saturation occurs when the power drops . The
17、other way is the use of physical or mathematical method foridentifying the characteristics of magnetizing inrush current, in order to lock in the power transformer protection devices drop, that the aforementioned avoid strategy. The two fatal road has its problems, capture does not produce magnetic
18、bias voltage closing angle of only two, namely, the two sinusoidal voltage peak point (90 or 270 ), if you deviate from these two points, partial there will be magnetic, which requires control of the closing part of all institutions (including circuit breakers) should be accurate, stable operating t
19、ime,because, as 1 millisecond time drift action, closing phaseangle of 18 will produce the error. In addition, three-phase voltage of the peak is not at the same time coming, but the difference between 120 , to completely eliminate the three-phase inrush current, must be time-phase three-phase circu
20、it breaker closing can be achieved, and the current operating rules prohibit such power will be lead to time-sharing-phasesplit-phase operation running, not to mention some circuit breakers in the sub-phase structure can not operate. dentification with the physical and mathematical methods of magnet
21、izing inrush current rather difficult, because the characteristics of magnetizing inrush current and a lot of factors, such as closing phase angle, the electromagnetic parameters of the transformer and so on. A large number of scholars and engineers through decades of unremitting effortsstill can no
22、t find an effective way, because of its high degree of difficulty, that is to avoid strategy difficult, the Achilles heel ofthis strategy is to tolerate the other excitation inrush current occurs, the pollution of its power grid and electrical equipment,there is still destructive. Transformer diagra
23、m 2-1 Figure 2-1 is a single-phase transformer structure, we can write the no-load voltage of the primary winding of the equation Where N1, R1, respectively, for the primary winding turns and the resistance (2.2)(2.1) can be rewritten as Where t = 0, U1, such as ignoring the initial phase angleresis
24、tor R1, which Let R1 = 0, we obtain the solution (2.3)-type equations have an expression for the magnetic flux Based on flux conservation theorem, in the closing momentsmagnetic flux can not change suddenly, you can find theintegration constant C. The amplitude of the total flux from equation (2.6)
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10 积分
下载 | 加入VIP,下载更划算! |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 外文翻译 外文文献 英文文献 变压器励磁涌流的抑制 外文 翻译 文献 英文 变压器 涌流 抑制