1、东北电力大学本科毕业论文摘要本课题题目为沈阳市某宾馆空调系统设计。此次设计的主要内容包括:对建筑功能的划分和使用要求,对餐厅、厨房、储藏室、客房的客房及通风设计。由概算结果确定各建筑功能房间的设计标准和设计方案,查找当地各种设计参数和设计标准,通过计算分析,咨询讨论,综合经济、性能、施工难度等等因素,确定最优方案。本设计计算部分从整栋楼的冷负荷计算开始,为了能够对冷负荷有全面的认识,此次设计采用计算法。从系统合理、选型合适、能源损耗等角度出发,并对宾馆中每一种类型的房间进行分析,从而得出合理的冷负荷。在完成方案的确定后,进行风系统和水系统的阻力计算,在计算过程中,综合经济因素,质量因素等确定管
2、材,确定风管水管管路路径,得出最不利路径的阻力,结合冷负荷,送风量等选择相应的空调末端产品以及辅助设备。关键字:宾馆空调系统;双螺杆冷水制冷机;风机盘管;新风系统V东北电力大学本科毕业论文Abstract This project is a hotel air conditioning system design in Shenyang City. The building designed in Shenyang is a five-storey hotel. The first layer is a restaurant, the height of witch is 4.5 m. The
3、 remaining four are the guestrooms, the height of witch is 3.3 m. Buildings total approximately 21.3 meters in height, with a total floor area of approximately 2200 square meters.The main contents of the design include: the allocation and requirements of the building function. The ventilation design
4、 of the dining room, kitchen, storage room, and guestroom .Budget for the results to determine design criteria and design of the building function rooms, Find a local variety of design parameters and design standards, determine the optimum solution through calculation and analysis, consultation and
5、discussion, the comprehensive economic performance, the difficulty of construction, among other factors.The computational part of this design begins from the whole building cooling load calculation. In order to be able to have a comprehensive understanding of the cooling load, the design uses the me
6、thod of calculation. In order to arrive at a reasonable cooling load we start from a systematic and rational selection of appropriate energy loss, and analysis the hotel room of every type.Initially identify the system program after understanding the building profile and design parameters and the co
7、oling load: For the reason of the hotels low-rise, the use of the cooling load is low, we chose a semi-centralized central air conditioning system. In order to be more economical commitment to the room cooling load and the moisture load, select the design of the air-water system. Specific design of
8、air the number of parameters, the air flow constant, the use of air source and room control requirements set. By calculating, the total cooling capacity is 180KW, apply a refrigeration unit with cold water chillers, air-cooled twin-screw Model RTAA-211, whose cooling capacity of 190kW,According to t
9、he function of the room, the whole building and a return air system and fan coil plus an independent air system. Because this arrangement can not only save more energy than the new air system, but also be controlled easier. Room ventilation is natural ventilation, especially the new air handling coi
10、l unit plus an independent air system to the indoor state point enthalpy online, directly to the indoor, do not bear the indoor load. Water system design: we refer to multiple instances of domestic and foreign, according to the present hotel building cooling load is smaller, the area of secondary an
11、d local climatic conditions decided to adopt a closed system with the process, and set the highest point in the system expansion tank.After the completion of the program is determined, the calculation of resistance of the air system and water system should be started. In the calculation process, the
12、 comprehensive economic factors, quality factors to determine the pipe to determine the path of the duct hose pipe to draw the most unfavorable path of resistance, combined with the cooling load, air supply, select the corresponding end of the air-conditioning products as well as auxiliary equipment
13、.We find a variety of manufacturers in the design process, product samples, get to know todays professional manufacturing level, and follow HVAC design guidelines and regulations, discuss the problems encountered in this design, and lessons learned. According to the design process and calculation re
14、sults, use the CAD to draw standard layer of air-conditioning system plan, water system, wind system diagram, Axonometric.Keywords: Hotel air conditioning system; Twin-screw cold water refrigerator; Fan coil; Fresh air system目录目 录摘要IIAbstractIII第1章 绪论11.1课题背景及研究意义11.2建筑空调系统节能国内外研究现状1第2章 工程概况及设计参数42.
15、1建筑资料42.2 夏季冷负荷的计算5 2.2.1 围墙的屋面传热冷负荷5 2.2.2 窗传热得热冷负荷6 2.2.3 窗日照得热冷负荷6 2.2.4 照明散热冷负荷6 2.2.5 设备(电脑)散热冷负荷72.2.6 人员散热冷负荷72.2.7夏季冷负荷计算表72.3夏季湿负荷的计算8第3章有关负荷计算93.1 传热系数的计算93.1.1 外墙和屋内传热系数的确定93.1.2 窗传热系数的确定93.2 有关夏季冷负荷的计算103.2.1 外墙和屋面传热冷负荷103.2.2 窗传热得热冷负荷103.2.3 窗日照得热冷负荷113.2.4 照明散热冷负荷113.2.5 设备散热冷负荷113.2.6
16、 人员散热冷负荷123.3 有关夏季湿负荷的计算123.3.1 人体散湿量123.4 有关冬季热负荷的计算133.4.1 围护结构热负荷133.4.2 房间湿负荷13第4章 方案的确定144.1 空调方案的确定及空调系统的划分144.1.1 空调方案的特点及确定144.1.2 空气处理过程144.2水系统的布置184.3风系统的布置19第5章 末端装置及新风机组的设备选型215.1风机盘管的选择215.2新风机组的选择225.3制冷机组的选择235.4末端通风口的选择计算23第6章 风系统的水力计算266.1通风管的布置和要求266.2风系统最不利环路计算26第7章 水系统的水力计算337.1
17、水系统的布置形式与工作原理337.2水系统最不利环路计算33第8章 其他设备的选择388.1空调系统消声设备选型388.2保温材料的选择388.3膨胀水箱的选择388.4冷冻水水泵的选择39结论40参考文献41致谢42第一章 绪论 第1章 绪论1.1课题背景及研究意义随着我国人民生活水平的不断提高,消费力增强。近年来修建了不少宾馆建筑,并且向多元化方向发展,建筑规模越来越大。装饰豪华、设施全面、多维服务,集住宿、商贸、娱乐、运动为一体的高级宾馆建筑也层出不穷1。宾馆是一个流动人口众多的公共场所,室内空气的温湿度、洁净度和新鲜空气量等,对客人的身体健康影响很大。因此,宾馆建筑设施的空气环境越来越
18、被卫生部门所重视。我国卫生防疫部门对宾馆建筑提出了卫生要求,对较大的重点宾馆还进行过监测,对一些已建的大中宾馆地点要求进行改造,增设通风设施或加建空气调节装置。宾馆建筑不断的增多,以及人们对室内空气的温湿度、洁净度和空气品质问题越来越重视1。由于能源的紧缺,节能问题越来越引起人们的重视。因此迫切需要为宾馆场所安装配置节能、健康、舒适的中央空调系统来满足人们对高生活水平的追求。中央空调是现代建筑必须具备的条件之一。中央空调能够改善和提高人们工作和居住环境的质量,改善和提高人们的生活和健康水平。近年来,各种大中型民用建筑供冷、供热的中央空调工程方兴未艾,越来越受到各行各业人们的重视。随着社会化大发
19、展,功能齐全的现代化建筑,尤其是高层建筑不断涌现,因此中央空调将会有更为广阔的发展前景。1.2建筑空调系统节能国内外研究现状中央空调在世界上已有百年的发展历史,在中国也有20多年的应用时间,然而真正引起国内企业关注还是近几年。目前国内市场中央空调领域竞争已经进入白热化阶段,随着价格战连绵不断,在家用空调领域几乎已经无利可图的企业纷纷开始在中央空调领域寻找新的发展空间和利润增长点。2003年中央空调市场容量将达到85亿元,2005年达到200亿元以上。市场空间迅速巨大,而利润至少是40%以上。这对于众多在市场上艰难逐利的企业,尤其是仍在价格战中挣扎的家电企业来说,无疑是极其诱人的。与家用空调行业
20、相比,中央空调仍保持较高利润空调,这使得由原来约克、大金、开利等国外品牌所占领的国内中央空调市场开始发生变化,国内一些品牌也纷纷进入这个领域。我国中央空调仍处于起步阶段,目前其销售对象主要集中在城市高收入消费群体和房地产开发商,由于其生产及安装成本较高,大范围普及尚需时日,这对争先上马该项目的企业不能不说是个考验。此外,与普通家用空调相比,中央空调对核心技术、资金要求更高,所以欲真正立足于该领域并非易事。在中央空调发展趋势中,健康、环保、节能也将是永远的主题。中国中央空调市场虽然还处于发展初期,但是不少企业已经在上述方面做了诸多尝试9。能源是整个经济系统的基本组成部份,作为一个能源消耗大国,美
21、国在节能和提高能源利用率方面投入了大量的人力、物力。在美国的整个能源消耗中,有约1/3以上消耗在建筑能耗上,这些能耗用来满足人们的热舒适、空气品质、提高人们的生活质量。美国暖通空调制冷工程师协会、美国制冷协会、美国冷却塔协会等组织、美国能源部以及众多暖通空调设备生产厂家如York, Carrier等都为建筑节能做出了很大贡献。特别是美国制冷设备生产厂商投入了大量的资源研究高性能冷水机组,使得冷水机组单位制冷量的能耗仅为20世纪70年代的62.3%。美国在空调冷源水系统方面的研究也卓有成效,在冷却水系统方面着重于降低冷却水流量,以达到减少冷却水泵能耗的目的。日本是一个资源贫困的国家,其主要能源来
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
20 积分
下载 | 加入VIP,下载更划算! |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- 宾馆 空调 系统 设计